Quiz Summary
0 of 133 questions completed
Questions:
Information
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading…
You must sign in or sign up to start the quiz.
You must first complete the following:
Results
Results
0 of 133 questions answered correctly
Your time:
Time has elapsed
You have reached 0 of 0 point(s), (0)
Earned Point(s): 0 of 0, (0)
0 Essay(s) Pending (Possible Point(s): 0)
Categories
- (other) 0%
- NFPA 72 0%
- NTC Brown Book 0%
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- 41
- 42
- 43
- 44
- 45
- 46
- 47
- 48
- 49
- 50
- 51
- 52
- 53
- 54
- 55
- 56
- 57
- 58
- 59
- 60
- 61
- 62
- 63
- 64
- 65
- 66
- 67
- 68
- 69
- 70
- 71
- 72
- 73
- 74
- 75
- 76
- 77
- 78
- 79
- 80
- 81
- 82
- 83
- 84
- 85
- 86
- 87
- 88
- 89
- 90
- 91
- 92
- 93
- 94
- 95
- 96
- 97
- 98
- 99
- 100
- 101
- 102
- 103
- 104
- 105
- 106
- 107
- 108
- 109
- 110
- 111
- 112
- 113
- 114
- 115
- 116
- 117
- 118
- 119
- 120
- 121
- 122
- 123
- 124
- 125
- 126
- 127
- 128
- 129
- 130
- 131
- 132
- 133
- Current
- Review
- Answered
- Correct
- Incorrect
-
Question 1 of 133
1. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 15 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 2 of 133
2. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 18 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 3 of 133
3. Question
Consider an area which has 8.6 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 4 of 133
4. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 5 of 133
5. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 20 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 6 of 133
6. Question
Consider a corridor which is 10 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 7 of 133
7. Question
Consider an area which has 10 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 8 of 133
8. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 9 of 133
9. Question
Consider a room with a smooth and level ceiling which is 15 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 10 of 133
10. Question
Consider a corridor which is 15 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 11 of 133
11. Question
Consider an area which has 20 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 12 of 133
12. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 13 of 133
13. Question
Consider a room with a smooth and level ceiling which is 10 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 14 of 133
14. Question
Consider a corridor which is 20 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 15 of 133
15. Question
Consider an area which has 30 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 16 of 133
16. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 15 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 17 of 133
17. Question
Consider a room with a smooth and level ceiling which is 18 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 18 of 133
18. Question
Consider a corridor which is 25 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 19 of 133
19. Question
Consider an area which has 60 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 20 of 133
20. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 20 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 21 of 133
21. Question
Consider a room with a smooth and level ceiling which is 20 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 22 of 133
22. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 1 second per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 23 of 133
23. Question
Consider a 120 feet x 150 feet room which has a ceiling surface with beams which are 15 inches deep and spaced at 4 feet apart. The ceiling is 14 feet AFF and level. The beams run the length of the room. Based on this a total of _____ detectors are required?
CorrectIncorrect -
Question 24 of 133
24. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 25 of 133
25. Question
Consider a 24 VDC fire alarm notification appliance circuit with 14 AWG solid coated copper conductor (approximately 3 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 26 of 133
26. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 2 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 27 of 133
27. Question
Consider a 120 feet x 150 feet room which has a ceiling surface with beams which are 24 inches deep and spaced at 4 feet apart. The ceiling is 14 feet AFF and level. The beams run the length of the room. Based on this a total of _____ detectors are required?
CorrectIncorrect -
Question 28 of 133
28. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 29 of 133
29. Question
Consider a 24 VDC fire alarm notification appliance circuit with 16 AWG solid coated copper conductor (approximately 5 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 30 of 133
30. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 4 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 31 of 133
31. Question
Consider a 120 feet x 150 feet room which has a ceiling surface with beams which are 24 inches deep and spaced at 4 feet apart. The ceiling is 14 feet AFF and level. The beams run the length of the room. Projected beam smoke detectors with a listed spacing of 60’ x 300’ are used. Based on this a total of _____ projected beam smoke detectors are required?
CorrectIncorrect -
Question 32 of 133
32. Question
Consider a room with a smooth and level ceiling which is 15 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 33 of 133
33. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 34 of 133
34. Question
Consider a 24 VDC fire alarm notification appliance circuit with 18 AWG solid coated copper conductor (approximately 8 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 35 of 133
35. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 36 of 133
36. Question
Consider a 120 feet x 150 feet room which has a ceiling surface with beams which are 24 inches deep and spaced at 10 feet apart. The ceiling is 14 feet AFF and level. The beams run the length of the room. Based on this a total of _____ detectors are required?
CorrectIncorrect -
Question 37 of 133
37. Question
Consider a room with a smooth and level ceiling which is 10 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 38 of 133
38. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 39 of 133
39. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 2 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 40 of 133
40. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 73 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 41 of 133
41. Question
Consider a 120 feet x 150 feet room which has a ceiling surface with beams which are 24 inches deep and spaced at 10 feet apart. The ceiling is 14 feet AFF and level. The beams run the length of the room. Based on this a total of _____ photobeam smoke detectors are required?
CorrectIncorrect -
Question 42 of 133
42. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 43 of 133
43. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 44 of 133
44. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 45 of 133
45. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 76 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 46 of 133
46. Question
Consider a room which is 50 feet wide and 95 feet in length. The ceiling is 10 feet AFF and smooth and level. The space has 30 air changes per hour. Based on this a total of _____ spot type smoke detectors are required?
CorrectIncorrect -
Question 47 of 133
47. Question
Consider a room with a smooth and level ceiling which is 18 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 48 of 133
48. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 49 of 133
49. Question
Consider a fire alarm notification circuit which has 500 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 50 of 133
50. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 79 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 51 of 133
51. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 52 of 133
52. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 53 of 133
53. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 54 of 133
54. Question
Consider a fire alarm notification circuit which has 250 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 55 of 133
55. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 80 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 56 of 133
56. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 57 of 133
57. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 58 of 133
58. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 15 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 59 of 133
59. Question
Consider an area which has 12 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 60 of 133
60. Question
Consider a horn which produces 84 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 61 of 133
61. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 62 of 133
62. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 10 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 63 of 133
63. Question
Consider an area which has 7.5 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 64 of 133
64. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 20 feet?
CorrectIncorrect -
Question 65 of 133
65. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 66 of 133
66. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 12 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 67 of 133
67. Question
Consider an area which has 15 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 68 of 133
68. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 69 of 133
69. Question
Consider a 24 VDC fire alarm notification appliance circuit with 14 AWG solid coated copper conductor (approximately 3 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 70 of 133
70. Question
Consider a 24 VDC fire alarm notification appliance circuit with 16 AWG solid coated copper conductor (approximately 5 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 71 of 133
71. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 72 of 133
72. Question
Consider a 24 VDC fire alarm notification appliance circuit with 18 AWG solid coated copper conductor (approximately 8 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 73 of 133
73. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 17 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 74 of 133
74. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 2 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 75 of 133
75. Question
Consider a ceiling which 14 feet AFF, and is level with beams for smoke detection purposes. The beams are 15 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 76 of 133
76. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 77 of 133
77. Question
Consider a ceiling which 16 feet AFF, and is level with beams for smoke detection purposes. The beams are 20 inches deep and spaced at 64 inches on center. Based on this, an adjustment of _____ is required?
CorrectIncorrect -
Question 78 of 133
78. Question
Consider a fire alarm notification circuit which has 500 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 79 of 133
79. Question
Consider a room with a smooth and level ceiling which is 15 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 80 of 133
80. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 40 feet?
CorrectIncorrect -
Question 81 of 133
81. Question
Consider a room with a smooth and level ceiling which is 20 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 82 of 133
82. Question
Consider a horn which produces 87 dBA at 10 feet. Based on this, the horn will produce _____ dBA at 80 feet?
CorrectIncorrect -
Question 83 of 133
83. Question
Consider a room with a smooth and level ceiling which is 20 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 84 of 133
84. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 15 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 85 of 133
85. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 1 second per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 86 of 133
86. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 12 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 87 of 133
87. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 4 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 88 of 133
88. Question
Consider an area which has 15 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 89 of 133
89. Question
Consider a 24 VDC fire alarm notification appliance circuit with 14 AWG solid coated copper conductor (approximately 3 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 90 of 133
90. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 10 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 91 of 133
91. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 2 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 92 of 133
92. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 18 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 93 of 133
93. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 12 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 94 of 133
94. Question
Consider an area which has 8.6 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 95 of 133
95. Question
Consider a 24 VDC fire alarm notification appliance circuit with 16 AWG solid coated copper conductor (approximately 5 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 96 of 133
96. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 97 of 133
97. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 4 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 98 of 133
98. Question
Consider a corridor which is 10 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 99 of 133
99. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 18 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 100 of 133
100. Question
Consider a 24 VDC fire alarm notification appliance circuit with 18 AWG solid coated copper conductor (approximately 8 ohms per 1K ft). The current is 4 amps in alarm. The notification appliances require a minimum of 20.4 volts to operate properly. Based on this, the maximum acceptable total length of conductors is _____ feet?
CorrectIncorrect -
Question 101 of 133
101. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 73 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 102 of 133
102. Question
Consider a corridor which is 15 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 103 of 133
103. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 76 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 104 of 133
104. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 2 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 105 of 133
105. Question
Consider a corridor which is 10 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 106 of 133
106. Question
Consider a corridor which is 20 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 107 of 133
107. Question
Consider a corridor which is 15 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 108 of 133
108. Question
Consider a fire alarm notification circuit which has 800 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 109 of 133
109. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 79 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 110 of 133
110. Question
Consider a fire alarm notification circuit which has 250 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 111 of 133
111. Question
Consider a corridor which is 25 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 112 of 133
112. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 80 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 113 of 133
113. Question
Consider a room with a smooth and level ceiling which is 10 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 114 of 133
114. Question
Consider a fire alarm notification circuit which has 500 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 115 of 133
115. Question
Consider a corridor which is 20 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 116 of 133
116. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 15 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 117 of 133
117. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 1 second per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 118 of 133
118. Question
Consider an area which has 12 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 119 of 133
119. Question
Consider a room with a smooth and level ceiling which is 18 feet AFF. Heat detectors with a listed spacing of 50 feet are used to provide automatic detection. Based on this, the maximum distance from the sidewall to the first row of ceiling mounted detectors is _____ feet?
CorrectIncorrect -
Question 120 of 133
120. Question
Consider a fire alarm notification circuit which has 250 feet total of solid coated copper conductors. The circuit is 24 VDC, and the current is 1 amps in alarm. The circuit is required to deliver 20.4 volts. Based on this, the appropriate wire size is _____ AWG? (Assume 1K ft of conductor: 18 AWG = 8 ohms, 16 AWG = 5 ohms, 14 AWG = 3 ohms, 12 AWG = 2 ohms)
CorrectIncorrect -
Question 121 of 133
121. Question
Consider a corridor which is 25 feet wide with a smooth and level ceiling. The maximum spacing between spot type smoke detectors is _____ feet?
CorrectIncorrect -
Question 122 of 133
122. Question
The design drawings show a room which is 100 feet x 150 feet with a ceiling height of 10 feet. The ceiling is smooth and level. Based on this, a total of _____ spot type smoke detectors are needed to cover this space?
CorrectIncorrect -
Question 123 of 133
123. Question
Consider the installation of an air sampling type smoke detection system. In this specific application, maximum air sampling transport time is 2 seconds per foot. Based on this, the farthest sampling port to the detector shall not exceed _____ feet?
CorrectIncorrect -
Question 124 of 133
124. Question
Consider an area which has 7.5 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 125 of 133
125. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 126 of 133
126. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 73 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 127 of 133
127. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 76 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 128 of 133
128. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 79 dBA at 40 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 129 of 133
129. Question
Consider speakers tapped at 1/8 watt and produce a sound level of 82 dBA at 10 feet. In order to produce a sound level of 70 dBA at 80 feet, the speakers should be tapped at _____ watt?
CorrectIncorrect -
Question 130 of 133
130. Question
Consider an area which has 12 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 131 of 133
131. Question
Consider an area which has 7.5 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 132 of 133
132. Question
Consider an area which has 15 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?
CorrectIncorrect -
Question 133 of 133
133. Question
Consider an area which has 8.6 air changes per hour. Based on this, spot type smoke detector spacing is _____ feet?